- GDK: Pcs - HRC: Pcs - LIC: Pcs - PST: Pcs
Description
| Device short name | ATV212 | 
|---|---|
| Product destination | Asynchronous motors | 
| Network number of phases | 3 phases | 
| Motor power kW | 45 kW | 
| Motor power hp | 60 hp | 
| Supply voltage limits | 323…528 V | 
| Supply frequency | 50...60 Hz - 5...5 % | 
| Line current | 83.8 A at 380 V 65.9 A at 480 V | 
| Range of product | Altivar 212 | 
| Product or component type | Variable speed drive | 
| Product specific application | Pumps and fans in HVAC | 
| Communication port protocol | Modbus LonWorks METASYS N2 BACnet APOGEE FLN | 
| [Us] rated supply voltage | 380...480 V - 15...10 % | 
| EMC filter | Class C2 EMC filter integrated | 
| IP degree of protection | IP21 | 
| Apparent power | 61.9 kVA at 380 V | 
|---|---|
| Continuous output current | 94 A at 380 V 94 A at 460 V | 
| Maximum transient current | 103.4 A for 60 s | 
| Speed drive output frequency | 0.5…200 Hz | 
| Speed range | 1…10 | 
| Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn | 
| Local signalling | 1 LED (red) for DC bus energized | 
| Output voltage | <= power supply voltage | 
| Isolation | Electrical between power and control | 
| Type of cable | Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC | 
| Electrical connection | VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14 L1/R, L2/S, L3/T: terminal 50 mm² / AWG 1/0 | 
| Tightening torque | 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) 24 N.m, 212 lb.in (L1/R, L2/S, L3/T) | 
| Supply | Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection | 
| Sampling duration | 2 ms +/- 0.5 ms F discrete 2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog | 
| Response time | FM 2 ms, tolerance +/- 0.5 ms for analog output(s) FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s) | 
| Accuracy | +/- 0.6 % (VIA) for a temperature variation 60 °C +/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C | 
| Linearity error | VIA: +/- 0.15 % of maximum value for input VIB: +/- 0.15 % of maximum value for input FM: +/- 0.2 % for output | 
| Analogue output type | FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits | 
| Discrete output type | Configurable relay logic: (FLA, FLC) NO - 100000 cycles Configurable relay logic: (FLB, FLC) NC - 100000 cycles Configurable relay logic: (RY, RC) NO - 100000 cycles | 
| Minimum switching current | 3 mA at 24 V DC for configurable relay logic | 
| Maximum switching current | 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) | 
| Discrete input type | F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm | 
| Discrete input logic | Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1) Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) | 
| Dielectric strength | 3535 V DC between earth and power terminals 5092 V DC between control and power terminals | 
| Insulation resistance | >= 1 mOhm 500 V DC for 1 minute | 
| Frequency resolution | Display unit: 0.1 Hz Analog input: 0.024/50 Hz | 
| Communication service | Read device identification (43) Write multiple registers (16) 2 words maximum Time out setting from 0.1 to 100 s Read holding registers (03) 2 words maximum Monitoring inhibitable Write single register (06) | 
| Option card | Communication card for LonWorks | 
| Power dissipation in W | 1253 W | 
| air flow | 429 m3/h | 
| Functionality | Mid | 
| Specific application | HVAC | 
| Variable speed drive application selection | Building - HVAC compressor for scroll Building - HVAC fan Building - HVAC pump | 
| Motor power range AC-3 | 30…50 kW at 380…440 V 3 phases 30…50 kW at 480…500 V 3 phases | 
| Motor starter type | Variable speed drive | 
| Discrete output number | 2 | 
| Analogue input number | 2 | 
| Analogue input type | VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits | 
| Analogue output number | 1 | 
| Physical interface | 2-wire RS 485 | 
| Connector type | 1 RJ45 1 open style | 
| Transmission rate | 9600 bps or 19200 bps | 
| Transmission frame | RTU | 
| Number of addresses | 1…247 | 
| Data format | 8 bits, 1 stop, odd even or no configurable parity | 
| type of polarization | No impedance | 
| Asynchronous motor control profile | Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 2 points Voltage/frequency ratio, 5 points Flux vector control without sensor, standard | 
| Torque accuracy | +/- 15 % | 
| Transient overtorque | 120 % of nominal motor torque +/- 10 % for 60 s | 
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 3200 s Automatic based on the load | 
| Motor slip compensation | Adjustable Not available in voltage/frequency ratio motor control Automatic whatever the load | 
| Switching frequency | 6...16 kHz adjustable 8...16 kHz with derating factor | 
| Nominal switching frequency | 8 kHz | 
| Braking to standstill | By DC injection | 
| Network frequency | 47.5...63 Hz | 
| Prospective line Isc | 22 kA | 
| Protection type | Overheating protection: drive Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor | 

 
                        
                       
                    