Overload, In > OC setting Sensitivity to phase loss Sensitivity to phase reverse Locked rotor, In > 3 times OC setting Phase unbalance, 50 %
Product specific application
Overcurrent protection
Analogue output range
4...20 mA
Network type
AC
Network frequency
50...60 Hz
protection ajustment range
0.5…10 A
Tripping threshold
0.5...6 A
Complementary
[Us] rated supply voltage
220 V AC
Mounting support
35 mm DIN rail Panel
Contacts type and composition
1 NO + 1 NC (OL)
Short-circuit and overload protection
By 4 A gG fuse
[Ue] rated operational voltage
600 V AC 50...60 Hz for power circuit conforming to UL 690 V AC 50...60 Hz for power circuit conforming to CSA 690 V AC 50...60 Hz for power circuit conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-4-1
Reset
Manual reset Electrical 0…1 s by interruption of power supply
Time delay type
O-Time: 0.3, 1...30 s, off (definite) D-Time: 1...120 s, off (definite) O-Time: 1...30 class (inverse) D-Time: 0...120 s (inverse)
Display type
7 segments LED
power consumption per relay
3 W
Connections - terminals
Control circuit: cable 2 x 1…1.5 mm²flexible with cable end - M3 Control circuit: cable 2 x 1…1.5 mm²flexible without cable end - M3 Control circuit: cable 1 x 1…2.5 mm²flexible with cable end - M3 Control circuit: cable 1 x 1…2.5 mm²flexible without cable end - M3
Tightening torque
Control circuit: 0.8...1.2 N.m on cable, 4.7 mm
height
71 mm
Width
70 mm
Depth
68 mm
Net weight
0.325 kg
Environment
standards
IEC 60947-4-1
IP degree of protection
IP20 conforming to IEC 60529
Ambient air temperature for operation
-20…60 °C conforming to IEC 60947-4-1
Ambient air temperature for storage
-30…80 °C
Operating altitude
2000 m
Fire resistance
650 °C conforming to IEC 60695-2-12 960 °C conforming to UL 94
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-7
Vibration resistance
4 gn on panel mounting conforming to IEC 60068-2-6 2 gn on 35 mm DIN rail conforming to IEC 60068-2-6
Dielectric strength
2 kV 50...60 Hz in between case and circuit conforming to IEC 60255-5 1 kV 50...60 Hz in between contact conforming to IEC 60255-5 2 kV 50...60 Hz in between circuit conforming to IEC 60255-5
Surge withstand
6 kV conforming to IEC 61000-4-5
Electromagnetic compatibility
Resistance to radiated electromagnetic fields: 10 V/m level 3 conforming to IEC 61000-4-3 Resistance to electrostatic discharge: 8 kV air, 6 kV contact conforming to IEC 61000-4-2 Resistance to fast transient: 2 kV conforming to IEC 61000-4-4 Conducted RF disturbances: 10 V conforming to EN 61000-4-6 Conducted RF disturbances: class A conforming to EN 55011
[Ith] conventional free air thermal current
5 A for control circuit
Permissible current
250 V, 5 A AC
You may also like
Recently viewed
Produk Berkualitas
Produk yang kami jual selalu asli, baru dan bergaransi
Hemat Waktu
Hemat waktu anda, cukup hubungi kami, kebutuhan anda akan kami antarkan ke tempat anda.
Staff Berpengalaman
Staff yang responsif dengan pengalaman 20 tahun akan selalu membantu anda
Lokasi Mudah
Kami memiliki 4 toko offline di lokasi yang strategis untuk mendukung melayani anda lebih baik lagi yaitu : - GMP LTC Glodok Jakarta Pusat - GMP Lippo Cikarang - GMP Jababeka Cikarang - GMP Deltamas Kabupaten Bekasi
Halo!
Silahkan bertanya kepada kami. Kami siap membantu anda