Description
Basic specifications
Accuracy guaranteed: 1 year
Measurement line | Single-phase, Three-phase (balanced with no distortion) |
---|---|
Measurement items | Voltage, Current, Voltage/Current peak, Active/Reactive/Apparent power, Power factor, Phase angle (*1), Frequency, Simple Active Energy Consumption (Single-phase) [With Z3210 installed (*2)] Voltage/Current harmonics |
AC voltage range | [Measurement range] 80.0 V to 600.0 V, Single range, Basic accuracy 45-66 Hz: ±0.7% rdg. ±3 dgt. (Frequency characteristics: 45 to 1 kHz, True RMS) |
AC current range | [Measurement range] 0.060 A to 600.0 A, 3 range, Basic accuracy 45-66 Hz: ±1.3% rdg. ±3 dgt. (Frequency characteristics: 45 to 1 kHz, True RMS) |
Power range | [Single phase] 05 kW to 360.0 kW Basic accuracy: ±2.0% rdg. ±7 dgt. (50/ 60 Hz, Power factor=1) [Balanced three-phase 3-wire] 0.020 kW to 623.5 kW Basic accuracy: ±3.0% rdg. ±10 dgt. (50/ 60 Hz, Power factor=1) [Balanced three-phase 4-wire] 0.040 kW to 1080 kW Basic accuracy: ±2.0% rdg. ±3 dgt. (50/ 60 Hz, Power factor=1) |
Harmonic levels | [With Z3210 installed (*2)] Voltage/Current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio |
Other functions | [Phase angle (*1)] lead -180.0° to lag 179.9°, [Power factor] -10 to 10 [Frequency] 45.0 Hz to 999.9 Hz, PEAK, Phase detection, MAX/MIN/AVG value display, Auto hold, electric meter comparison, unbalanced 3-phase power estimate display, etc. |
Dustproof and waterproof | IP50 (for measurement of current in insulated conductors or storage in completely dry conditions) |
Power supply | LR03 Alkaline battery ×2 Continuous use: approx. 25 hr (without Z3210 installed), approx. 18 hr. (with Z3210 installed and using wireless communications) Other conditions: 100 A AC measurement, backlight off, 23°C reference value |
Core jaw dia. | φ 46 mm (1.81 in), Jaw dimensions: 92 mm (3.62 in) W x 18 mm (0.71 in) D mm |
Dimensions and mass | 65 mm (2.56in) W × 241 mm (9.49in) H × 35 mm (1.38in) D, 450 g (15.9 oz) |
Included accessories | Connection Cord L9257 ×1, LR03 Alkaline battery ×2, Carrying Case C0203 ×2, Instruction Manual ×2, Operating Precautions ×1 |
- *1:Phase angle obtained from zero cross of current and voltage.
- *2:Harmonics can be displayed with our free app GENNECT Cross.
Countries and regions where wireless operation is currently supported (CM3286-01)
Last update: November 2022
Countries and regions where wireless operation is currently supported | Austria, Bangladesh, Belgium, Bulgaria, Canada, Chile, Colombia, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Georgia, Germany, Greece, Hong Kong, Hungary, Iceland, India, Indonesia, Ireland, Israel, Italy, Japan, Kenya, Korea, Latvia, Liechtenstein, Lithuania, Luxembourg, Macao, Malta, Myanmar, Netherlands, Norway, Peru, Philippines, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Thailand, Turkey, United Kingdom, United States, Vietnam |
|||||
---|---|---|---|---|---|---|
Note | Use of devices that emit radio radiation requires approval in the country of use. Thus, use of the instrument in a country or region where they have not been approved may be subject to penalty as a violation of law. |