- GDK: Pcs - HRC: Pcs - LIC: Pcs - PST: Pcs
 
Description
| range | 
  TeSys 
  | 
 |
|---|---|---|
| product name | 
  TeSys D 
  | 
 |
| product or component type | 
  Contactor 
  | 
 |
| device short name | 
  LC1D 
  | 
 |
| contactor application | 
  Motor control 
 Resistive load  | 
 |
| utilisation category | 
  AC-1 
 AC-4 AC-3  | 
 |
| poles description | 
  3P 
  | 
 |
| power pole contact composition | 
  3 NO 
  | 
 |
| [Ue] rated operational voltage | 
  Power circuit: <= 690 V AC 25...400 Hz 
 Power circuit: <= 300 V DC  | 
 |
| [Ie] rated operational current | 
  9 A (at <60 ��C) at <= 440 V AC AC-3 for power circuit 
 25 A (at <60 ��C) at <= 440 V AC AC-1 for power circuit  | 
 |
| motor power kW | 
  2.2 kW at 220...230 V AC 50/60 Hz (AC-3) 
 4 kW at 380...400 V AC 50/60 Hz (AC-3) 4 kW at 415...440 V AC 50/60 Hz (AC-3) 5.5 kW at 500 V AC 50/60 Hz (AC-3) 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) 2.2 kW at 400 V AC 50/60 Hz (AC-4)  | 
 |
| motor power HP (UL / CSA) | 
  1 hp at 230/240 V AC 50/60 Hz for 1 phase motors 
 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors  | 
 |
| control circuit type | 
  AC at 50/60 Hz 
  | 
 |
| [Uc] control circuit voltage | 
  380 V AC 50/60 Hz 
  | 
 |
| auxiliary contact composition | 
  1 NO + 1 NC 
  | 
 |
| [Uimp] rated impulse withstand voltage | 
  6 kV conforming to IEC 60947 
  | 
 |
| overvoltage category | 
  III 
  | 
 |
| [Ith] conventional free air thermal current | 
  25 A (at 60 ��C) for power circuit 
 10 A (at 60 ��C) for signalling circuit  | 
 |
| Irms rated making capacity | 
  250 A at 440 V for power circuit conforming to IEC 60947 
 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1  | 
 |
| rated breaking capacity | 
  250 A at 440 V for power circuit conforming to IEC 60947 
  | 
 |
| [Icw] rated short-time withstand current | 
  105 A 40 ��C - 10 s for power circuit 
 210 A 40 ��C - 1 s for power circuit 30 A 40 ��C - 10 min for power circuit 61 A 40 ��C - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit  | 
 |
| associated fuse rating | 
  10 A gG for signalling circuit conforming to IEC 60947-5-1 
 25 A gG at <= 690 V coordination type 1 for power circuit 20 A gG at <= 690 V coordination type 2 for power circuit  | 
 |
| average impedance | 
  2.5 mOhm - Ith 25 A 50 Hz for power circuit 
  | 
 |
| [Ui] rated insulation voltage | 
  Power circuit: 690 V conforming to IEC 60947-4-1 
 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified  | 
 |
| electrical durability | 
  0.6 Mcycles 25 A AC-1 at Ue <= 440 V 
 2 Mcycles 9 A AC-3 at Ue <= 440 V  | 
 |
| power dissipation per pole | 
  1.56 W AC-1 
 0.2 W AC-3  | 
 |
| Front cover | 
  With 
  | 
 |
| mounting support | 
  Plate 
 Rail  | 
 |
| standards | 
  CSA C22.2 No 14 
 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508  | 
 |
| product certifications | 
  UL 
 CSA DNV GL RINA CCC BV GOST LROS (Lloyds register of shipping)  | 
 |
| connections - terminals | 
  Power circuit: screw clamp terminals 1 cable(s) 1���4 mm��flexible without cable end 
 Power circuit: screw clamp terminals 2 cable(s) 1���4 mm��flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1���4 mm��flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1���2.5 mm��flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1���4 mm��solid without cable end Power circuit: screw clamp terminals 2 cable(s) 1���4 mm��solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1���4 mm��flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1���4 mm��flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1���4 mm��flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1���2.5 mm��flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1���4 mm��solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1���4 mm��solid without cable end  | 
 |
| tightening torque | 
  Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat �� 6 mm 
 Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat �� 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2  | 
 |
| operating time | 
  12...22 ms closing 
 4...19 ms opening  | 
 |
| safety reliability level | 
  B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 
 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1  | 
 |
| mechanical durability | 
  15 Mcycles 
  | 
 |
| maximum operating rate | 
  3600 cyc/h 60 ��C 
  | 
 
| coil technology | 
  Without built-in suppressor module 
  | 
 |
|---|---|---|
| control circuit voltage limits | 
  0.3...0.6 Uc (-40���70 ��C):drop-out AC 50/60 Hz 
 0.8...1.1 Uc (-40���60 ��C):operational AC 50 Hz 0.85...1.1 Uc (-40���60 ��C):operational AC 60 Hz 1...1.1 Uc (60���70 ��C):operational AC 50/60 Hz  | 
 |
| inrush power in VA | 
  70 VA 60 Hz cos phi 0.75 (at 20 ��C) 
 70 VA 50 Hz cos phi 0.75 (at 20 ��C)  | 
 |
| hold-in power consumption in VA | 
  7.5 VA 60 Hz cos phi 0.3 (at 20 ��C) 
 7 VA 50 Hz cos phi 0.3 (at 20 ��C)  | 
 |
| heat dissipation | 
  2���3 W at 50/60 Hz 
  | 
 |
| auxiliary contacts type | 
  type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 
 type mirror contact 1 NC conforming to IEC 60947-4-1  | 
 |
| signalling circuit frequency | 
  25...400 Hz 
  | 
 |
| minimum switching current | 
  5 mA for signalling circuit 
  | 
 |
| minimum switching voltage | 
  17 V for signalling circuit 
  | 
 |
| non-overlap time | 
  1.5 ms on de-energisation between NC and NO contact 
 1.5 ms on energisation between NC and NO contact  | 
 |
| insulation resistance | 
  > 10 MOhm for signalling circuit 
  | 
 |
| contact compatibility | 
  M2 
  | 
 |
| compatibility code | 
  LC1D 
  | 
 |
| motor power range | 
  0���0.5 kW at 100���120 V 3 phases 
 0.55���1 kW at 100���120 V 3 phases 0���0.5 kW at 200���240 V 3 phases 0.55���1 kW at 200���240 V 3 phases 1.1���2 kW at 200���240 V 3 phases 0���0.5 kW at 380���440 V 3 phases 0.55���1 kW at 380���440 V 3 phases 1.1���2 kW at 380���440 V 3 phases 2.2���3 kW at 380���440 V 3 phases 4���6 kW at 380���440 V 3 phases 0���0.5 kW at 480���500 V 3 phases 0.55���1 kW at 480���500 V 3 phases 1.1���2 kW at 480���500 V 3 phases 2.2���3 kW at 480���500 V 3 phases 4���6 kW at 480���500 V 3 phases 0���0.5 kW at 525���690 V 3 phases 0.55���1 kW at 525���690 V 3 phases 1.1���2 kW at 525���690 V 3 phases 2.2���3 kW at 525���690 V 3 phases 4���6 kW at 525���690 V 3 phases  | 
 |
| motor starter type | 
  Direct on-line contactor 
  | 
 
| IP degree of protection | 
  IP20 front face conforming to IEC 60529 
  | 
 |
|---|---|---|
| protective treatment | 
  TH conforming to IEC 60068-2-30 
  | 
 |
| pollution degree | 
  3 
  | 
 |
| ambient air temperature for operation | 
  -40���60 ��C 
 60���70 ��C with derating  | 
 |
| ambient air temperature for storage | 
  -60���80 ��C 
  | 
 |
| operating altitude | 
  0...3000 m 
  | 
 |
| fire resistance | 
  850 ��C conforming to IEC 60695-2-1 
  | 
 |
| flame retardance | 
  V1 conforming to UL 94 
  | 
 |
| mechanical robustness | 
  Vibrations contactor open: 2 Gn, 5...300 Hz 
 Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor open: 10 Gn for 11 ms Shocks contactor closed: 15 Gn for 11 ms  | 
 |
| height | 
  77 mm 
  | 
 |
| width | 
  45 mm 
  | 
 |
| depth | 
  86 mm 
  | 
 |
| net weight | 
  0.32 kg 
  | 
 
| Package 1 Weight | 
  0.351 kg 
  | 
 |
|---|---|---|
| Package 1 Height | 
  0.500 dm 
  | 
 |
| Package 1 width | 
  0.920 dm 
  | 
 |
| Package 1 Length | 
  1.120 dm 
  | 
 
| Sustainable offer status | 
  Green Premium product 
  | 
 |
|---|---|---|
| REACh Regulation | ||
| REACh free of SVHC | 
  Yes 
  | 
 |
| EU RoHS Directive | 
  Compliant 
 EU RoHS Declaration  | 
 |
| Toxic heavy metal free | 
  Yes 
  | 
 |
| Mercury free | 
  Yes 
  | 
 |
| RoHS exemption information | ||
| China RoHS Regulation | 
  
 China RoHS declaration 
 Pro-active China RoHS declaration (out of China RoHS legal scope)  | 
 |
| Environmental Disclosure | ||
| Circularity Profile | ||
| WEEE | 
  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins 
  | 
 |
| PVC free | 
  Yes 
  | 
 

                        
                      
                    