- GDK: Pcs - HRC: Pcs - LIC: Pcs - PST: Pcs
 
Description
| range of product | 
  Zelio Control 
  | 
 |
|---|---|---|
| product or component type | 
  Modular measurement and control relays 
  | 
 |
| relay type | 
  Multifunction control relay 
  | 
 |
| product specific application | 
  For 3-phase supply 
  | 
 |
| relay name | 
  RM17TE 
  | 
 |
| relay monitored parameters | 
  Undervoltage and overvoltage in window mode 
 Asymmetry Phase sequence Phase failure detection  | 
 |
| time delay | 
  Adjustable 0.1...10 s, +/- 10 % of the full scale value 
  | 
 |
| switching capacity in VA | 
  1250 VA 
  | 
 |
| measurement range | 
  208...480 V voltage AC 
  | 
 
| reset time | 
  1500 ms time delay 
  | 
 |
|---|---|---|
| maximum switching voltage | 
  250 V AC 
 250 V DC  | 
 |
| minimum switching current | 
  10 mA at 5 V DC 
  | 
 |
| maximum switching current | 
  5 A AC 
 5 A DC  | 
 |
| supply voltage limits | 
  183���528 V AC 
  | 
 |
| control circuit voltage limits | 
  - 12 % + 10 % Un 
  | 
 |
| power consumption in VA | 
  0���22 VA at 400 V AC 50 Hz 
  | 
 |
| control circuit frequency | 
  50...60 Hz +/- 10 % 
  | 
 |
| output contacts | 
  1 C/O 
  | 
 |
| nominal output current | 
  5 A 
  | 
 |
| measurement voltage limits | 
  183���528 V AC 
  | 
 |
| hysteresis | 
  2 % 
  | 
 |
| delay at power up | 
  650 ms 
  | 
 |
| maximum measuring cycle | 
  150 ms measurement cycle as true rms value 
  | 
 |
| threshold adjustment voltage | 
  -2...-17 % in the range 220 V AC 
 +2...+17 % in the range 480 V AC -2...-12 % in the range 208 V AC 2...20 % of Un selected  | 
 |
| voltage range | 
  208...480 V phase to phase 
  | 
 |
| adjustment of asymmetry threshold | 
  5...15 % of Un selected 
  | 
 |
| repeat accuracy | 
  0.5 % for input and measurement circuit 
 3 % for time delay  | 
 |
| measurement error | 
  < 0.05 %/��C with temperature variation 
 < 1 % over the whole range with voltage variation  | 
 |
| phase failure sensitivity | 
  0.7 Un 
  | 
 |
| response time | 
  < 200 ms (in the event of a fault) 
  | 
 |
| marking | 
  CE 
  | 
 |
| overvoltage category | 
  III conforming to IEC 60664-1 
  | 
 |
| insulation resistance | 
  > 500 MOhm at 500 V DC conforming to IEC 60255-5 
 > 500 MOhm at 500 V DC conforming to IEC 60664-1  | 
 |
| [Ui] rated insulation voltage | 
  400 V conforming to IEC 60664-1 
  | 
 |
| supply frequency | 
  50/60 Hz +/- 10 % 
  | 
 |
| operating position | 
  Any position without derating 
  | 
 |
| connections - terminals | 
  Screw terminals, 1 x 0.5...1 x 4 mm�� (AWG 20...AWG 11) solid without cable end 
 Screw terminals, 2 x 0.5...2 x 2.5 mm�� (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm�� (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm�� (AWG 24...AWG 16) flexible with cable end  | 
 |
| tightening torque | 
  0.6���1 N.m conforming to IEC 60947-1 
  | 
 |
| housing material | 
  Self-extinguishing plastic 
  | 
 |
| local signalling | 
  LED (green) for power ON 
 LED (yellow) for relay ON  | 
 |
| mounting support | 
  35 mm symmetrical DIN rail conforming to EN/IEC 60715 
  | 
 |
| electrical durability | 
  100000 cycles 
  | 
 |
| mechanical durability | 
  30000000 cycles 
  | 
 |
| operating rate | 
  <= 360 operations/hour full load 
  | 
 |
| utilisation category | 
  AC-12 conforming to IEC 60947-5-1 
 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1  | 
 |
| safety reliability data | 
  MTTFd = 502.2 years 
 B10d = 470000  | 
 |
| width | 
  17.5 mm 
  | 
 |
| net weight | 
  0.13 kg 
  | 
 
| electromagnetic compatibility | 
  Emission standard for industrial environments conforming to EN/IEC 61000-6-4 
 Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Immunity for industrial environments conforming to EN/IEC 61000-6-2  | 
 |
|---|---|---|
| standards | 
  EN/IEC 60255-1 
  | 
 |
| product certifications | 
  GOST 
 C-Tick CSA UL GL  | 
 |
| directives | 
  89/336/EEC - electromagnetic compatibility 
 73/23/EEC - low voltage directive  | 
 |
| ambient air temperature for storage | 
  -40���70 ��C 
  | 
 |
| ambient air temperature for operation | 
  -20���50 ��C 
  | 
 |
| relative humidity | 
  95 % at 55 ��C conforming to IEC 60068-2-30 
  | 
 |
| vibration resistance | 
  0.35 mm (f= 5���57.6 Hz) conforming to IEC 60068-2-6 
 1 gn (f= 57.6���150 Hz) conforming to IEC 60255-21-1  | 
 |
| shock resistance | 
  15 gn for 11 ms conforming to IEC 60255-21-1 
  | 
 |
| IP degree of protection | 
  IP20 (terminals) conforming to IEC 60529 
 IP30 (casing) conforming to IEC 60529  | 
 |
| pollution degree | 
  3 conforming to IEC 60664-1 
  | 
 |
| dielectric test voltage | 
  2 kV, 1 min AC 50 Hz conforming to IEC 60255-5 
 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1  | 
 |
| non-dissipating shock wave | 
  4 kV conforming to IEC 60255-5 
 4 kV conforming to IEC 60664-1 4 kV conforming to IEC 61000-4-5  | 
 

                        
                      
                    