Sensitivity to phase failure Overload Imax > Isetting Locked rotor, mechanical jamming I > 3 x Isetting
Product compatibility
LC1D09...D38
Network type
AC
[Us] rated supply voltage
200...240 V AC
Thermal protection adjustment range
0.3…1.5 A
[Ue] rated operational voltage
600 V AC 50/60 Hz for power circuit conforming to CSA 600 V AC 50/60 Hz for power circuit conforming to UL 690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1
Quantity per set
Set of 10
Complementary
Network frequency
50...60 Hz
Mounting support
Direct on contactor Rail
Tripping threshold
0.3...1.3 A
Surge withstand
6 kV conforming to IEC 61000-4-5
Contacts type and composition
1 C/O
[Ith] conventional free air thermal current
3 A for control circuit
Protection type
BS fuse 3 A - for control circuit GB2 circuit breaker 3 A - for control circuit GG fuse 3 A - for control circuit
Maximum power
28 W at 110 V DC conforming to IEC 60947 28 W at 220 V DC conforming to IEC 60947 55 W at 24 V DC conforming to IEC 60947 55 W at 48 V DC conforming to IEC 60947 140 VA at 48 V AC conforming to IEC 60947 360 VA at 110 V AC conforming to IEC 60947 360 VA at 220 V AC conforming to IEC 60947 70 VA at 24 V AC conforming to IEC 60947
[Ui] rated insulation voltage
Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL Power circuit: 690 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV
Phase failure sensitivity
< 3 s
Reset
Automatic reset 120 s fixed Electrical by interruption of power supply for minimum 0.1 s Manual reset
Time range
0.2...10 s - O-time knob 0.3...10 s - O-time knob 0.5..30 s - D-time knob
Signalling function
2 LEDs
Connections - terminals
Control circuit: cable 1 x 1…25 mm²flexible with cable end Control circuit: cable 1 x 1…25 mm²flexible without cable end Power circuit: cable 1 x 1…4 mm²flexible with cable end Power circuit: cable 1 x 1.5…10 mm²flexible without cable end Power circuit: lug-clamp 1 x 1…4 mm²flexible with cable end Power circuit: lug-clamp 1 x 1.5…10 mm²flexible without cable end Control circuit: cable 2 x 1…25 mm²flexible with cable end Control circuit: cable 2 x 1…25 mm²flexible without cable end Control circuit: lug-clamp 1 x 1…25 mm²flexible with cable end Control circuit: lug-clamp 1 x 1…25 mm²flexible without cable end Control circuit: lug-clamp 2 x 1…25 mm²flexible with cable end Control circuit: lug-clamp 2 x 1…25 mm²flexible without cable end
Tightening torque
Control circuit: 0.6...1.2 N.m on lug-clamp Power circuit: 2 N.m on cable
height
67.5 mm
Width
45 mm
Depth
67.5 mm
Net weight
0.172 kg
Environment
standards
IEC 60255-6 IEC 60947
product certifications
CSA UL GOST
Protective treatment
TH conforming to IEC 60068
IP degree of protection
IP20 conforming to IEC 60529
Ambient air temperature for operation
-25…60 °C conforming to IEC 60947-4-1
Ambient air temperature for storage
-30…80 °C
Operating altitude
2000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Shock resistance
15 gn 11 ms conforming to IEC 60068-2-7
Vibration resistance
4 gn conforming to IEC 60068-2-6
Dielectric strength
2 V 50 Hz conforming to IEC 60255-5
Resistance to electrostatic discharge
6 kV in indirect mode 8 kV in air
Resistance to radiated fields
10 V/m level 3
Resistance to fast transients
2 kV
Disturbance radiated/conducted
10 V conforming to EN 61000-4-6 Class A conforming to EN 55011
You may also like
Recently viewed
Produk Berkualitas
Produk yang kami jual selalu asli, baru dan bergaransi
Hemat Waktu
Hemat waktu anda, cukup hubungi kami, kebutuhan anda akan kami antarkan ke tempat anda.
Staff Berpengalaman
Staff yang responsif dengan pengalaman 25 tahun akan selalu membantu anda
Lokasi Mudah
Kami memiliki 4 toko offline di lokasi yang strategis untuk mendukung melayani anda lebih baik lagi yaitu : - GMP LTC Glodok Jakarta Pusat - GMP Lippo Cikarang - GMP Jababeka Cikarang - GMP Deltamas Kabupaten Bekasi
Halo!
Silahkan bertanya kepada kami. Kami siap membantu anda