Current Voltage Frequency Power factor Energy Active and reactive power
supply voltage
90...450 V AC 45...65 Hz 100...300 V DC
Network frequency
60 Hz 50 Hz
[In] rated current
5 A 1 A
type of network
3P + N 1P + N 3P
Maximum power consumption in VA
11 VA at 415 V
Ride-through time
80 ms 120 V AC typical 100 ms 230 V AC typical 100 ms 415 V AC typical 50 ms 125 V DC typical
Display type
Monochrome graphic LCD
Display resolution
128 x 128 pixels
Sampling rate
64 samples/cycle
Measurement current
50…8500 mA
Analogue input type
Voltage (impedance 5 MOhm) Current (impedance <= 0.3 mOhm)
Measurement voltage
35…760 V AC 45...65 Hz between phases 20…400 V AC 45...65 Hz between phase and neutral
Frequency measurement range
45…65 Hz
Number of inputs
0
Measurement accuracy
Active energy +/- 0.5 % Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Frequency +/- 0.05 % Power factor +/- 0.5 Current +/- 0.5 % Voltage +/- 0.5 % Apparent energy +/- 0.5 % Reactive power +/- 2 %
Accuracy class
Class 0.5S active energy conforming to IEC 62053-22
Number of outputs
1 pulse (energy)
Communication port protocol
-
Communication port support
-
data recording
Min/max of instantaneous values Time stamping
Connections - terminals
Voltage circuit: screw terminal block4 Control circuit: screw terminal block2 Current transformer: screw terminal block6 Input/output circuit: screw terminal block6 RS485 link: screw terminal block4
Mounting mode
Flush-mounted
Mounting support
Framework
Product certifications
CE conforming to IEC 61010-1 CULus conforming to UL 61010-1
Width
96 mm
Depth
72 mm
height
96 mm
Net weight
380 g
Environment
Electromagnetic compatibility
Limits for harmonic current emissions class A conforming to IEC 61000-3-2 Electrostatic discharge level 4 conforming to IEC 61000-4-2 Conducted RF disturbances level 3 conforming to IEC 61000-4-6 Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 Conducted and radiated emissions class B conforming to EN 55022 Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 Surge immunity test conforming to IEC 61000-4-5 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
IP degree of protection
IP54 display: conforming to IEC 60529 IP30 rear: conforming to IEC 60529
Relative humidity
5…95 % at 50 °C non-condensing
Pollution degree
2
Ambient air temperature for operation
-25…70 °C meter -20…70 °C display -25…-20 °C (with reduced performance) display
Ambient air temperature for storage
-40…85 °C
Operating altitude
2000 m CAT III
You may also like
Recently viewed
Produk Berkualitas
Produk yang kami jual selalu asli, baru dan bergaransi
Hemat Waktu
Hemat waktu anda, cukup hubungi kami, kebutuhan anda akan kami antarkan ke tempat anda.