Relay Phase Control Hilang Phase & Urutan Phase Schneider RM17TG20 (2C/O 5A) 208-480VAC
Save 43%
SchneiderSKU: 0005252
Description
range of product |
Zelio Control
|
|
---|---|---|
product or component type |
Modular measurement and control relays
|
|
relay type |
Control relay
|
|
product specific application |
For 3-phase supply
|
|
relay name |
RM17TG
|
|
relay monitored parameters |
Phase sequence
Phase failure detection (2 or more phase cut) |
|
time delay |
Without
|
|
switching capacity in VA |
1250 VA
|
|
measurement range |
208...440 V voltage AC
|
maximum switching voltage |
250 V AC
250 V DC |
|
---|---|---|
minimum switching current |
10 mA at 5 V DC
|
|
supply voltage limits |
183���484 V AC
|
|
control circuit voltage limits |
- 12 % + 10 % Un
|
|
power consumption in VA |
0���22 VA at 400 V AC 50 Hz
|
|
voltage detection threshold |
< 100 V AC
|
|
control circuit frequency |
50...60 Hz +/- 10 %
|
|
output contacts |
2 C/O
|
|
nominal output current |
5 A
|
|
measurement voltage limits |
183���484 V AC
|
|
delay at power up |
650 ms
|
|
voltage range |
183...484 V
|
|
response time |
<= 130 ms (in the event of a fault)
|
|
marking |
CE
|
|
overvoltage category |
III conforming to IEC 60664-1
|
|
insulation resistance |
> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1 |
|
[Ui] rated insulation voltage |
400 V conforming to IEC 60664-1
|
|
supply frequency |
50/60 Hz +/- 10 %
|
|
operating position |
Any position without derating
|
|
connections - terminals |
Screw terminals, 1 x 0.5...1 x 4 mm�� (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm�� (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm�� (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm�� (AWG 24...AWG 16) flexible with cable end |
|
tightening torque |
0.6���1 N.m conforming to IEC 60947-1
|
|
housing material |
Self-extinguishing plastic
|
|
local signalling |
LED (yellow) for relay ON
|
|
mounting support |
35 mm symmetrical DIN rail conforming to EN/IEC 60715
|
|
electrical durability |
10000 cycles
|
|
mechanical durability |
30000000 cycles
|
|
operating rate |
<= 360 operations/hour full load
|
|
utilisation category |
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
|
safety reliability data |
B10d = 850000
MTTFd = 924.6 years |
|
width |
17.5 mm
|
|
net weight |
0.13 kg
|
electromagnetic compatibility |
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Immunity for industrial environments conforming to EN/IEC 61000-6-2 |
|
---|---|---|
standards |
EN/IEC 60255-1
|
|
product certifications |
GOST
C-Tick UL CSA GL |
|
directives |
73/23/EEC - low voltage directive
89/336/EEC - electromagnetic compatibility |
|
ambient air temperature for storage |
-40���70 ��C
|
|
ambient air temperature for operation |
-20���50 ��C
|
|
relative humidity |
95 % at 55 ��C conforming to IEC 60068-2-30
|
|
vibration resistance |
0.35 mm (f= 5���57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6���150 Hz) conforming to IEC 60255-21-1 |
|
shock resistance |
15 gn for 11 ms conforming to IEC 60255-21-1
|
|
IP degree of protection |
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529 |
|
pollution degree |
3 conforming to IEC 60664-1
|
|
dielectric test voltage |
2 kV, 1 min AC 50 Hz
|
|
non-dissipating shock wave |
4 kV
|